LaSalle RO Quiz

20 Random Questions, RO only, all Exam Years

 

Results

#1. Unit 2 is at full power Suppression Pool (SP) Cooling is in operation Average pool temperature is increasing RCIC testing is in progress If SP temperature continues to rise; the unit is required to immediately stop RCIC testing if SP temperature exceeds (1) degrees F; or immediately place the reactor mode switch in SHUTDOWN if SP temperature exceeds (2) degrees F.

#2. Unit 1 is in a refueling outage. A single fuel bundle is being loaded into the core. The signal-to-noise ratio is 15 to 1. The MINIMUM count rate to verify the required SRMs operable is __ counts per second.

#3. Unit 1 was at 100% RTP when all CW pumps tripped and were unable to be restarted.Assuming no operator actions, after 60-minutes you would expect to observe tO automatically control reactor pressure.

#4. Automatic fire suppression is delayed from activation in the DG rooms to…

#5. The ADS accumulators are at a higher pressure than the SRV accumulators because . . .

#6. Given the following plant conditions: – Reactor recirculation loop B pump tripped – Power and flow in the allowable region of Technical SpecificationsThermal Limits: 1. Average Planar Linear Heat Generation Rate 2. Minimum Critical Power Ratio 3. Linear Heat Generation Rate 4. Maximum Allowable Power RatioWhich of the above thermal limits must be adjusted?

#7. What is the significance of the 1/4-inch diameter black dot located on the label forControl Room recorder 1TR-CM037A AVG SP TEMP? The black dot signifies that the recorder . . .

#8. Unit 1 is in a Refueling Outage. HPCS is running for a post-maintenance test. LPCS is being drained for a pump inspection. A RHR is running in the SDC mode of operation. C RHR pump discharge valve repair is in progress. Annunciator 1PM13J-B304; RB SE-SW EQUIP DRN SUMP TROUBLE is LIT.o R1438 RB SE DRN SUMP TROUBLE is indicated on the SER display. Annunciator 1PM13J-402; RB SOUTH FLOOR DRN SUMP TROUBLE just LIT.o R1437 RB S FLR DRN SUMP TROUBLE is indicated on the SER display.Which of the following systems should be checked FIRST to determine the cause of thelisted alarms?

#9. A reactor startup following a 21 day refueling outage is in progress on Unit 2: The NSO determines the reactor is critical and stops rod withdrawal. Reactor power continues to rise with no rod motion. One hour later; reactor power turns and begins to lower.In accordance with LGP 1-1 Attachment L; Precautions to Be Used Before; During; and After Pulling Critical (1) Why did reactor power start lowering? (2) Which of the following would indicate the reactor has returned to subcritical?

#10. Reactor startup is in progress. The reactor is NOT critical. SRM s read as follows: Channel: A B C D Counts Per Second: 2×103 3×103 2×103 5×103 Predict the effect of a loss of the SRM C High Voltage Power Supply; AND what would be the necessary operator action? EFFECT NECESSARY OPERATOR ACTION

#11. The mode switch is inSTARTUP. IRMs are all on range 5 or 6.During performance of a surveillance for the mode switch, SRMA is moved out ofOPERATE and placed in theSTANDBY position.Which of the following alarm response procedures must be entered?

#12. Assume that AC Electrical Power is lost to the Division 1; 125 vde BatteryChargers.Continuing to operate without restoring AC Electrical Power to the Division 1; 125 vdeBattery Chargers will result in …

#13. Which of the following identifies the level instruments that input into RWLC?1. Upset2. Wide Range3. Narrow Range

#14. Unit 1 is operating at 100% power with 250 VDC MCC 121Y de-energized; when the supply breaker to MCC 135X-3 trips. What is the status of the Plant Process Computer (PPC) Uninterruptible Power Supply (UPS) AND what must occur in order for it to be powered from its preferred; normal source?

#15. Unit 1 is shutdown with HPCS in standby. Suppression pool water level is being lowered from normal level to – 9 feet. Predict the impact of this change on the High Pressure Core Spray (HPCS) discharge Line Pressure. HPCS discharge line pressure will&

#16. Unit 1 is operating at rated power. Which of the following components could be eligible to have independent verification waived? A Danger tag to be hung on the…

#17. Select the answer below that reflects the recommended verbalization of component 1FC088Awhen giving an order to manipulate the component.

#18. Unit 1 is at 100% power. The function switch for the ” A” RBM is placed in ” STANDBY” . What; if any; rod blocks will be applied?

#19. You have been directed by the Unit Supervisor to place the 1B DGMaintenance-Auto Transfer Switch in the MAINT position.Where is the switch located?

#20. The Unit 1 reactor is shutdown with head installed and the following conditions: – Coolant temperature is 170F – ‘B’ train residual heat removal is in shutdown cooling operation at 7000 gpm – both recirculation pumps out of service – reactor water level is being maintained at +50 inches on the Shutdown RangeIf an inadvertent PCIS Group 6 isolation occurs and the isolation signal can NOT be cleared; inorder to minimize thermal stratification of the bottom reactor vessel head AND enhance RPVmoderator temperature monitoring; the operators would . . .

Previous
Finish